Brass Tube Fittings

Qualified matching pipe:

  • Copper tube per ASTM 8819 Type K
  • L Drawn copper tube per ASTM B88 Type K, L and M

Pressure-temperature rating:

Nominal
Fitting Size
(TXX)
Tube
O.D.
Qualified Wall
Thickness
K/L/M
Insertion
Depth
Pre-Install,
A
Insertion
Depth
Post-Install,
B
Outside
Diameter

C
Minimum
Straight
Run Before
Obstruction,
E
1/2" (T08)
0.625
.049/ .040 / .028
1.23
0.98
0.91
1.64
5/8" (T10)
0.750
.049/ .042
1.41
1.10
1.02
1.91
3/4" (T12)
0.857
.065/ .045 / .032
1.55
1.19
1.19
1.99
1" (T16)
1.125
.065/ .050 / .035
2.04
1.56
1.53
2.60
1-1/4" (T20)
1.375
.065/ .055 / .042
2.31
1.77
1.86
2.81
1-1/2" (T24)
1.625
.072/ .060 / .049
2.64
2.02
2.21
3.20
2" (T32)
2.125
.083/ .070 / .058
3.44
2.63
2.88
4.05

 

Exceeds Required Temperature of 1000° F

Presssure rating should be derated at elevated temperature.
Fittings meet 1000° F integrity test.
See specification FS-BR for details.

 

Brass "Thru Bore"